![](/uploads/1/2/5/5/125516108/101815690.jpg)
Description
Registration is only available to Gent Approved System Integrators. For your access to be approved. Installation and Operating manual for the Vigilon panel: 3. Fire detection and alarm system up to 2km loop. Local Manual Call Point 5 EN54 information 6. Vigilon Compact Fire System GENT 2015.
Vigilon Compact analogue addressable panels fully comply with EN54 parts 2 and 4 and can be specified with 1 or 2 detection loops, each capable of accommodating 200 devices comprising of repeat panels, interfaces, manual
call points, sensors and sounders. It’s capable of being included in multi-panel networks with other compact panels and alongside the 4 and 6 loop Vigilon control panels. Vigilon Compact offers the familiar advantages of combined sensor-sounders and loop powered beam detection with integral short circuit isolators fitted into every loop device
call points, sensors and sounders. It’s capable of being included in multi-panel networks with other compact panels and alongside the 4 and 6 loop Vigilon control panels. Vigilon Compact offers the familiar advantages of combined sensor-sounders and loop powered beam detection with integral short circuit isolators fitted into every loop device
The panel is fully compatible with Gent’s innovative S-Quad multi-sensor technology which combines speech, sounder and visual alarm in one device. It’s also compatible with Gent’s S-Cubed alarm devices offering loop powered, integrated sound, speech and a fully certified EN54-23 class leading visual alarm.
Key Features
- Advanced loop card technology supporting 2km loop with standard 1.5mm2 cable (increases to 2.5km with 2.5mm2 cable)
- Vigilon Compact is a 1 to 2 loop panel which manages up to 200 devices per loop
- High capacity for loop powered alarm devices with up to 800mA alarm load or 100 integrated sensor sounder and visual alarm devices
- PC based commissioning tools allow complex fire plans to be configured
- Zonal LED indication on every panel provides compliance with BS 5839 Part 1: 2002
- Serial communication ports allow connectivity to paging and BMS systems with no additional interface hardware
- The control panel has a simple user interface with LCD screen providing accurate information in an emergency
- Multiple panel networks can be programmed seamlessly as one system, allowing for flexible design and system management
- Flexible programming options are available at the panel
- Stainless steel door option available that provides a discreet and luxurious feel to buildings demanding a highly aesthetic look
CONTROL PANEL SPECIFICATION
![Gent Gent](http://docplayer.es/docs-images/40/5827404/images/page_11.jpg)
Max Number of Loops | 2 | ||||
Loop Capacity | 200 Devices per loop, Alarm load 800mA per loop (max across both loops 1.4A) | ||||
Networking Capacity | Up to 31 panels in a single domain (multiple domains can extend a network up to 200 panels) | ||||
Ingress Protection | IP31 | ||||
Approx Weight | 16.6 Kg (including batteries) | ||||
Operating Temperature | 0ºC to +45ºC | ||||
Relevant Standards | EN54 Parts 2 & 4 | ||||
Batteries | 2 x 12V @ 12Ah | ||||
Battery Standby | 24 Hours + 30 minutes alarm (Dependant on device loading – please use the battery standby calculator to confirm actual standby) | ||||
Supply Voltage | 216V – 253V 50Hz | ||||
Power Consumption | 140 W | ||||
Aux DC supply | 24V 200 mA (must be considered when calculating battery standby) | ||||
Cable Entry | Top and rear | ||||
Dimensions (mm) | 403 (H) x 338 (W) x 101 (D) | ||||
Auxiliary Contacts | Programmable to activate on Fire, Fault or Disablement. (1 x SPCO 1 x DPCO) | ||||
Sounder Circuits | 2 circuits @ 250mA each | ||||
Monitored input | 1 input which is programmable to perform a logical action via a command build | ||||
Communication ports | 1 x RS485 2 x RS232 } selectable functions | ||||
Approvals | Certified to EN54 Parts 2 & 4 |